|
TOP Server Version 4.83.225 - December 20, 2002 - Release Notes
The following enhancements and fixes are included in this release of the TOP Server. Download your
free update/upgrade by clicking here.
Driver Updates:
Driver Updates: In general, all driver revisions have been bumped up one revision to provide for a new internal
interface with servermain.exe.
|
Allen-Bradley ControlLogix (4.50.59)
|
- Added L5K import support for Predefined Data Types: SFC_ACTION, SFC_STEP,
and SFC_STOP. (RSLogix5000 Version 11) - Fixed an L5K import parsing bug that would cause an import abort if the keyword TAG was found in a ROUTINE declaration
- Fixed data coercing bug in which bits could not be referenced for non-BITARRAY elements (ie. DINTARRAY[0]). Symptoms: Tags would be deactivated and error posted: "Datatype
'Boolean' is illegal for this tag." Boolean is considered an invalid data type for non-BITARRAY elements (ie. DINTARRAY[0]) and is only valid for BITARRAY elements. Bits within a
non-BITARRAY element (ie. DINTARRAY[0].0) are valid and must be Boolean.
|
|
GE SNP (4.21.44)
|
- Fixed issue importing SNF descriptions that are not wrapped in quotes.
|
|
GE SNPX (4.21.44)
|
- Fixed issue importing SNF descriptions that are not wrapped in quotes.
|
|
GE Ethernet (4.71.42)
|
- Fixed issue importing SNF descriptions that are not wrapped in quotes.
|
|
Modbus Serial (4.66.73)
|
- Added new model to support the Daniel S500 Flow meter. The Daniel S500 has specific
memory ranges that support 32 bit floats, booleans and a true 64 bit Double float. The driver has been modified with the addition of a new model to support Daniel S500 in terms of addressing
and specific additions to the communications state machine for the support of a Double.
|
|
Siemens Simatic 505 Serial (4.41.35)
|
-After adding the Array support as noted in the previous version, the customer like that
so much they wanted even bigger arrays. The problem is the TI 505 protocol only allows for very small request for data. The user wanted a 100 word array in V memory. To do this the driver
needed to be modified to allow a multi-pass read or write to occur in order to support this 100 word array.
|
|
Siemens 3964R (4.11.22)
|
- Bug fix: Data block KT values were not converted from Siemens time format correctly on
reads. Writes worked correctly.
|
|
Yokogawa Darwin Serial (4.03.27)
|
- Added Ethernet Encapsulation feature to allow use of terminal/device servers.
|
|
Yokogawa CX Ethernet (4.00.07)
|
- New Driver
|
|
Yokogawa HR 2400 Serial (4.01.08)
|
- New Driver
|
|
|